model Fsd-331
Combination Fire smoke dampers
APPLICATION
Steel Airfoil Blades
Model FSD-331 is a high performance combination fire smoke damper
with extremely low leakage. High strength airfoil blades ensure the
lowest resistance to airflow in HVAC systems with velocities to 2000
fpm (10.2 m/s) and pressures to 4 in. wg (1 kPa). Model FSD-331 may
be installed vertically (with blades running horizontal) and is rated for
airflow and leakage in either direction.
UL 555S Leakage Class I
UL555 3 Hour Fire Resistance Rating
Model FSD-331 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
RATINgs
National Fire Protection Association
UL 555 Fire Resistance Rating
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
Fire Rating:
3 hours
IBC International Building Codes
ICBO uniform Building Codes
CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
Dynamic Closure Rating: Actual ratings are size dependent
Max. Velocity:
Max. Pressure:
up to 2000 fpm (10.2 m/s)
4 in. wg (1 kPa)
UL555S Leakage Rating
Leakage Class:
I
Operational Rating:
Max. Velocity:
Max. Pressure:
Actual ratings are size dependent
up to 3000 fpm (15.2m/s)
4 in. wg (1 kPa)
Maximum Temperature: 350°F (177°C)- depending upon the
actuator
“uL CLAssIFIed (see complete marking on
product)”
“uL CLAssIFIed to Canadian safety standards
(see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
sTANdARd CONsTRuCTION
Frame:
5 in. x 1 in. (127mm x 25 mm)
galvanized steel hat channel with
reinforced corners. A low profile head
and sill are used on sizes less than
17 in. (432mm)
Greenheck Fan Corporation certifies that the
model FSD-331 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
Blades:
Seals:
Double skin airfoil shape of
galvanized steel with full length
structural reinforcement. 14 ga.
(2 mm) equivalent thickness.
Extruded silicone rubber blade seals
Flexible stainless steel jamb seals.
Concealed in jamb.
AMCA Certified Ratings Programs. The
R
AMCA Certified Ratings Seal applies to air
performance ratings only.
Linkage:
Closure Device:
Axles:
RRL 165°F (74°C)
1⁄2 in. (13mm) dia. plated steel.
Bronze sleeve type.
Bearings:
sIze LImITATIONs:
minimum size:
8 in. W x 6 in. H
(203 mm W x 152mm H)
maximum size (Vertical Only):
Single Section:
32 in. W x 36 in.H
(813mm W x 914mm H) or
30 in. W x 48 in. H
(762mm x 1219mm)
120 in. W x 96 in. H
(3048mm W x 2438mm H)
Multiple Section:
LH
OPTIONAL FeATuRes:
H*
• RRL/OCI (Open closed indication switches)
• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's
available
• TOR (remote override closure allows damper to perform smoke
management functions during a fire emergency.)
• Electric or pneumatic actuators to accomplish smoke management
and system functions.
W*
• POC retaining angles
RH
• Smoke detectors
• Momentary Switch
*W&H dimensions furnished approximately 1/4 in. ( 6 mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
• Security Bars
• Sealed transitions and sleeves
AmCA 5.2 Pressure drop
Fsd-331
5D
*
36x36
12x48
48x12
12x12
24x24
* Sizes are in inches.
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.03
0.12
0.26
0.46
0.72
1.04
1.41
1.84
500
0.01
0.06
0.12
0.22
0.34
0.49
0.67
0.87
500
0.01
0.06
0.12
0.22
0.34
0.49
0.67
0.88
500
0.01
0.05
0.12
0.21
0.33
0.48
0.65
0.85
500
1000
1500
2000
2500
3000
3500
4000
0.02
0.08
0.18
0.33
0.51
0.74
1.00
1.31
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
Greenheck Fan Corporation certifies that the
model FSD-331 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air
performance ratings only.
R
AmCA 5.3 Pressure drop
Fsd-331
5D
6D
*
24x24
12x12
36x36
48x12
12x48
* Sizes are in inches.
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
500
1000
1500
2000
2500
3000
3500
4000
0.01
0.06
0.13
0.23
0.37
0.53
0.73
0.95
500
0.01
0.02
0.06
0.10
0.16
0.23
0.32
0.42
500
1000
1500
2000
2500
3000
3500
4000
0.01
0.02
0.05
0.09
0.14
0.21
0.29
0.38
500
1000
1500
2000
2500
3000
3500
4000
0.01
0.02
0.06
0.10
0.16
0.24
0.33
0.43
500
0.01
0.04
0.10
0.18
0.29
0.42
0.57
0.74
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
Greenheck Fan Corporation certifies that the
model FSD-331 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air
performance ratings only.
R
AmCA 5.5 Pressure drop
Fsd-331
*
36x36
48x12
12x12
12x48
24x24
* Sizes are in inches.
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
(in. wg)
500
1000
1500
2000
2500
3000
3500
4000
0.04
0.18
0.42
0.75
1.17
1.68
2.29
2.09
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.13
0.29
0.52
0.81
1.17
1.60
2.14
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.12
0.27
0.48
0.75
1.08
1.48
1.93
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.12
0.27
0.49
0.77
1.11
1.51
1.97
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.14
0.32
0.57
0.89
1.28
1.75
2.29
Greenheck Fan Corporation certifies that the
model FSD-331 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air
performance ratings only.
R
Application data
damper sleeve dimensional data
The drawings below and corresponding table show the position of the FSD-331 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for
installation of retaining angles and duct connections.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be
positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.
1
1
/2" max.
"A" Dimension
in. (mm)
All Dampers*
Standard
Maximum
12 (305)
12 (305)
33/4"
7 3/16 (183)
12 (305)
When H is 11 in. (279mm) or
less with OCI, RRL, or TOR
*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed within the
wall. The damper blades, when closed should be contained within
the wall.
6"
Varies
53/8"
LH
RH
A
5"
Sleeve Length
T*
Right hand drive is shown
Left hand drive available upon request
Actuators and Accessories
S
space envelopes
Externally mounted actuators always require space
outside of the damper sleeve. The “S” dimension
illustrates the clearance required for various available
actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below
the sleeve. “B” and “T” dimensions are worst case
clearance requirements for some dampers less
than 18 in. (457 mm) high. All damper sizes under
18 in. (457mm) high do not require these worst case
clearances. If space availability above or below the
damper sleeve is limited, each damper size should be
individually evaluated.
B*
B*
T*
Actuator Type/Model
S
With
With
RRL, RRL/OCI, or TOR RRL, RRL/OCI, or TOR
120 Volt AC
ML-4XXX Series Honeywell
MS-4XXX Series Honeywell
MS-4120 Series Honeywell
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
¾ in.(19mm)
3/8 in. (10mm)
3/8 in. (10mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
24 Volt AC
ML-8XXX Series Honeywell
MS-8XXX Series Honeywell
MS-8120 Series Honeywell
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
¾ in.(19mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
Pneumatic (25 psi min.)
331-4551 Powers
331-2976 Powers
MK2-7121 Invensys
1 in. (25mm)
2 3/8 in. (60mm)
3 3/4 in. (95mm)
6¼ in. (159mm)
12 1/8 in. (308mm)
16½ in. (419mm)
6½ in. (165mm)
9¼ in. (235mm)
10 in. (254mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .
damper sizing Information
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The
following figures show maximum damper section size and assembly configurations for multi-section dampers.
Double Section
Single Section
48 in.
(1219mm)
36 in.
(914mm)
30 in. (762mm)
60 in. (1524mm)
32 in. (813mm)
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the
Transitioned damper
dimensions
FSD-331 can be supplied in a factory sleeve with round or oval transitions on both ends
of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show
overall damper size.
D*+
2 in. (51mm) +T
s
W*+ 2 in. (51mm)+T
s
W*+ 2 in. (51mm)+T
s
D*+ 2 in. (51mm)+T
s
H*+ 2 in. (51mm)+T
H*+ 2 in. (51mm)+T
s
s
H*
H*
21/8in.
21/8in.
(54mm)
These dimensions are furnished
*
21/8in.
(54mm)
(54mm)
approximately 1/4 in. (6mm) undersize,
except round and oval dimensions
which are approximately 1/8 in.(3mm)
undersize.
*
W
W*
D*
16 in. (406mm)
Min.
16 in. (406mm)
Min.
16 in. (406mm)
Min.
T
= (2)(Sleeve Thickness)
s
TYPE R
TYPE O
TYPE C
specifications
Combination Fire Smoke Dampers meeting the following
Damper blades shall be of the double skin airfoil type and shall
have an equivalent thickness of 14 ga. (2mm) . Damper frame shall
be galvanized steel formed into a structural hat channel shape with
reinforced corners. Bearings shall be sintered bronze sleeve type
rotating in extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a tighter
seal against leakage as pressure on either side of the damper
increases. Jamb seals shall be stainless steel compression type.
Blades shall be completely symmetrical relative to their axle pivot
point, presenting identical resistance to airflow in either direction or
pressure on either side of the damper.
specifications shall be furnished and installed where shown on
plans and/or as described in schedules. Dampers shall meet the
requirements of NFPA 80, 90A, 92A, 92B, 101, and 105 and further
shall be tested, rated and labeled in accordance with the latest
edition of UL Standards 555 and 555S. Dampers shall have a UL555
fire rating of 3 hours and be of low leakage design qualified to
UL 555S Leakage Class I.
Each damper/actuator combination shall have a UL555S elevated
temperature rating of 350° F (177°C) minimum and shall be
operational and dynamic rated to operate at maximum design air
flow at its installed location. Each damper shall be supplied with
an appropriate actuator installed by the damper manufacturer at
the time of damper fabrication. Damper actuator shall be (specifier
select one of the following) electric type for 120 (24 or 230) volt
operation or pneumatic type for 25 psi minimum (30 psi maximum)
operation.
Damper must be rated for mounting vertically (with blades running
horizontal) and be UL 555S rated for leakage and airflow in either
direction through the damper. Each damper shall be supplied with
a 165°F (74°C) RRL. Testing and ratings to be in accordance with
AMCA standard 500-D.
The basis of design is Greenheck Model FSD-331.
Copyright © 2008 Greenheck Fan Corporation
FSD-331 Rev 1 March 2008
|